An indirect evaporative cooler incorporating a porous ceramic and a heat pipe was described. Experiments were carried out to examine the effects of various ceramic properties, such as porosity, wall thickness, and outside diameter. Use of the cooler for a chilled ceiling in an environmental chamber was also investigated. A temperature drop of 3.8oC per square metre of ceramic surface area was achieved for an 18 m chamber.
Member of
ISSN
1726-6742
Citation
Riffat, S., & Zhu, J. (2004). Experimental investigation of an indirect evaporative cooler consisting of a heat pipe embedded in porous ceramic. The Journal of Engineering Research, 1 (1), 46-52.
Arabic abstract
تقدم الورقة وصفا لمبرد بالتبخر اللامباشر لمكون من أنبوب حراري مضمن في فخار نفاذ. أجريت تجارب لاختبار تأثير خصائص الفخار كالنافذية وسمك الجدران والقطر الخارجي للأنبوب الفخاري على فاعلية المبرد. كما تمت دراسة فاعلية المبرد في تبريد غرفة قياس سعة 18 م3 وقد لوحظ انخفاض في درجة الحرارة بمقدار 8 و3 درجة على مقياس سلسيس لكل متر مربع من الفخار.